Manual · JVA Z-series

JVA energizer manual: status lights, flash codes and keypad

JVA's Z-series energizers show their state on a row of coloured lights and a voltage display, and can be run from JVA's 4-line LCD keypad in the house. Most owner questions come down to three things: what a light or a number of flashes means, how to silence and clear an alarm, and what the keypad commands do. Here are the answers from JVA's own manuals, with the wiring and installer settings left to the installer.

Our promise

2-year warranty and a compliance certificate on every new electric fence we install

A technician shining a torch on the terminals of an open electric fence energiser box in a garage

Z-series specifications

JVA Z-series energizers, from JVA's manuals
ModelZonesPeak voltage, no loadPeak energyPulses
Z1119.0 kV1.4 J0.8 a second
Z1319.8 kV2.8 J0.9 a second
Z14 and Z14R19.0 kV4 J (2.5 J in a group)0.9 a second
Z1818.5 kV8 J0.9 a second
Z11419.5 kV14 J0.75 a second
Z2828 J (4 J a channel)

All run on 16 to 18 V AC from a transformer, with a 12 V sealed lead-acid battery, and JVA's manual is explicit that they can't operate without the battery. The battery charger floats at 14 V. If the battery falls below 6.5 V, the energizer stops but still draws a little current. Larger sites use JVA's monitors instead of, or alongside, energizers: the ZM20 and ZM50 control and monitor 20 to 50 sectors, and the ZLM4 watches up to four low-voltage loops.

What the status lights mean

On the Z13, Z14, Z14R and Z18:

  • Power: on whenever the energizer has power.
  • Armed: on when it's armed and pulsing; flashing in low power mode.
  • Fence: flashes green when it's on and the voltage is good; flashes red if the voltage drops below the alarm level; stays red during a fence alarm.
  • Gate: flashes red while the gate is open; stays red during a gate alarm.
  • Status: flashes a number for a service fault (see the next section).

The Z114 has the same idea per zone (Armed 1, Fence 1, Gate 1). On newer firmware (version 7.77 onwards), the fence and gate lights stay lit after an alarm until the alarm memory is cleared or the energizer is re-armed, so a light that's on doesn't always mean the fault is still there.

A technician shining a torch on the terminals of an open electric fence energiser box in a garage

Status light flash codes

JVA Z-series Status LED codes, from the installer manual
FlashesMeaningWhat to do
1Tamper: the lid is off or was openedHave the lid refitted properly
2Mains failureRestore the power to the transformer
3Low or bad batteryCharge it, or have it replaced
4A fault on the circuit boardService or repair

A tamper or a board fault disarms the energizer and raises the alarms. A mains failure or a low battery doesn't: the fence keeps running on the battery. But without mains, the battery eventually runs down; after 4 warning beeps the energizer drops into low power mode to keep going, and if the charge keeps falling it stops. When the mains returns and the battery recovers, it re-arms itself, again after 4 beeps. Minor errors clear themselves once their cause is gone. If an error made the fence stop pulsing for a moment, JVA says disarming and re-arming clears it; if it keeps coming back, the energizer needs a service.

When the fence alarms, and silencing it

When the fence is armed and the return voltage drops below the alarm level for more than a few pulses (3 by default), the zone light flashes and then stays on, the siren and keypad beeper sound, and any outputs linked to the fence alarm switch on, which can signal your house alarm and armed response. A gate input that opens and stays open past its delay does the same.

The siren runs for the on and off cycles the installer set and then stops, but the strobe stays on until the alarm is dealt with. If the cause goes away, the siren stops at the end of its current cycle.

To silence it, enter your PIN and #. That silences the alarm without disarming: the armed light stays on and the fence is ready for the next alarm, while the zone lights show where it happened. Entering the PIN and # again disarms. On a Z14 or Z18 with a key switch, disarming with the key also resets the alarm. The zone light stays lit until the alarm memory is cleared.

The battery

When the mains fails, the keypad's power light goes off; in a long outage it starts to flash as the battery runs low, and the energizer's status light flashes 3 times when the battery needs replacing. JVA's rules for the battery: a 12 V sealed lead-acid rechargeable only, in a well-ventilated enclosure, because charging lead-acid batteries can give off explosive gas.

Replacing it means switching off the energizer, disconnecting the 16 V supply and opening the cover, which exposes the energizer's terminals: leave that to a technician. Old batteries go to a recycler, never into the bin.

The JVA 4-line keypad

JVA's PTE0240 keypad has a backlit four-line screen that scrolls through a summary page (the installer's details, the time, whether the site is armed and whether all is OK) and then a page for each energizer or monitor, with its zone name, voltages and any alarm or trouble. Each screen shows for about 5 seconds; # pauses the scrolling for 20 seconds and pressing it again moves on a screen. A new alarm or trouble jumps the display to that zone and beeps.

It has quick Arm and Disarm keys (followed by your PIN), a Menu key, a 500-entry event log with date and time, and a menu with Mute Siren, Clear Alarms, Show Event Log, Arm Low Power, Arm High, a test menu and a list of shortcuts.

Everyday JVA keypad commands, from the keypad manual
What it doesKeys
Arm or disarmYour PIN, #
Arm all zones / disarm all zones (multi-zone sites)PIN, \* 1 0 # / PIN, \* 2 0 #
All zones to low power / back to high powerPIN, \* 4 1 # / PIN, \* 4 2 #
Clear the alarm memory\* 1 #
Siren test\* 6 3 #
Battery test\* 6 4 #
Show the stored joules\* 6 7 #
Show the keypad model and firmware\* 9 #

If the summary page says Keypad Not Polled, the keypad hasn't been introduced to the master energizer, which is an installer's job; on a site with two keypads, someone may simply be using the other one, so wait a few seconds.

A hand entering a code on a steel keypad pedestal beside a driveway gate

Two zones and bigger sites

The Z28 splits its output into two channels of 4 joules each, so the fence becomes two zones with their own lights and alarms, and each can be armed separately with a key switch or from the keypad. The keypad's zone commands (arm or disarm a single zone, or switch one zone to low power) use the zone number in place of the 0 for "all zones".

For estates and factories, JVA's monitors watch many sections of fence and report to the same keypads: the ZM20 and ZM50 for 20 to 50 sectors, the ZM1 alongside a standard energizer, and the ZLM4 for four low-voltage loops.

When to call us, and JVA's PDFs

Call us when the status light shows 4 flashes, the fence light flashes red after you've checked the line for plants and breaks, the battery code won't clear after a day on mains, or the keypad says Not Polled and nobody has touched it. Don't open the energizer or change its settings yourself. We repair JVA energizers and keypads, replace batteries, earths and insulators, and upgrade older fences. All our spare parts are genuine, and every repair carries our six-month guarantee on our repairs.

In shops, a JVA Z11 (1 zone) costs about R3 070 (Takealot) and a JVA Z13 (1 zone) about R3 370 (Takealot) (Prices checked October 2026). Your exact price is set in a free quote before any work starts. No call-out fee when we do the work. If no work is done, a R650 call-out fee applies.

The official PDFs, from JVA:

More on JVA repairs and prices is on JVA, and alarms in general on electric fence alarms.

Questions

JVA energizer questions

What do 3 flashes mean on a JVA energizer?

Three flashes of the status light mean the battery is low or bad: let it charge on mains, and if the code doesn't clear, the battery needs replacing. One flash is a tamper, two a mains failure and four a board fault. See the flash codes.

How do I silence a JVA electric fence alarm?

Enter your PIN and #: the alarm stops but the fence stays armed. Entering the PIN and # again disarms it. The zone light stays on until the alarm memory is cleared. See silencing the alarm.

Can a JVA energizer work without a battery?

No. JVA's manual says the Z-series can't operate without its 12 V sealed lead-acid battery, which also carries the fence through a power cut. See the battery.

Why does my JVA keypad say it is not polled?

The keypad hasn't been introduced to the master energizer, which an installer sets up; if there's a second keypad on site, someone may be using it, so wait a few seconds and try again. See the keypad.